Electrical connection
Leuze electronic
LES 36
48
TNT
35/7-2
4
V
6.3.3
Connection X3 - switching inputs/outputs (LES 36…/VC6)
Preferably, please use the ready-made cables "KS S-M12-8A-P1-…", see
Chapter 15.2.4.
Switching outputs of connection X3
Out1 to Out4 are each a logic combination of analysis results of the individual AWs. This
logic operation is defined in LRSsoft (see chapter 9.4 "Parameter settings/Parameters tab").
Up to 16 different logic combinations of the AWs and respective result mappings on Out1
to Out4 can be combined into inspection tasks.
Switching inputs of connection X3
The three InSel1-3 switching inputs are used to select inspection tasks 0-7. "000" means
inspection task 0, "001" inspection task 1, etc. The changeover time between two inspection
tasks is < 100ms
Note!
The Inspection Tasks 8-15 can be switched via LRSsoft, PROFIBUS or Ethernet. The setting
via Ethernet overwrites the inspection task set via input InSel1-3.
X3 (8-pin socket, A-coded)
Pin
Name
Core color
Comment
1
Out4
wh
Output detection result 4
2
Out3
br
Output detection result 3
3
GND
gn
Ground
4
Out2
ye
Output detection result 2
5
Out1
gr
Output detection result 1
6
InSel3
pi
Selection Inspection Task Bit 3
(MSB)
7
InSel2
bu
Selection Inspection Task Bit 2
8
InSel1
RD
Selection Inspection Task Bit 1
(LSB)
Table 6.5:
Pin assignment X3
Out4
InSel 1
Out3
GND
Out2
InSel 3
InSel 2
Out1
X3
7
8
M12 socket
(A-coded)