Technical data
Leuze electronic
MSI-TRMB
44
Table 14.3:
Inputs/outputs
14.2 Dimensions
Figure 14.1: MSI-TRMB-01 dimensions
Resistance
11.7 Ohm/km
Max. cable lengths (reset circuit)
250 m
Max. cable lengths (input circuit)
250 m
Max. load of control outputs S11, S21
IMax ≤ 50 mA / 24 V DC, short-circuit proof
Transmitter activation
PNP (high active)
Receiver input
Input current approx. 5 mA
Start inputs S34, S35 (depending on application)
Typ. input current 8 mA / 24 V DC
Safety inputs S12, S22
Typ. input current 8 mA / 24 V DC
Reset input
Input current approx. 5 mA
Contactor monitoring (EDM)
Typ. input current 8 mA / 24 V DC
S31 signal output
PNP transistor output, ≤ 50 mA / 24 V DC, short-
circuit proof
"Error" signal output
PNP transistor output, 100 mA, short-circuit and
polarity reversal protection
Safety output
2 potential-free NO contacts
5 … 250 V AC/DC, 5 mA … 3 A
Fuse
External with max. 3 A F or 3 A T
Overvoltage category
3 for rating voltage 300 V AC acc. to EN 50178
99.0
22.5
114.1
111.5
S11 S12 S21 S22
S31 S32 S33 S34
A1
S35 S36 A2
13
14
23
24
OUT1 IN1
PWR
OUT2 IN2
Fault
13 14 23 24
MSI-TRMB