Electrical connection
Leuze electronic
MSI-TRMB
25
EDM configuration
Further information see chapter 4.7.
Table 7.3:
EDM configuration
ª
Trigger a reset (software reset via the start button if the device is in the error state, or by briefly switching
off the voltage supply at A1 / using reset button connected in series to the supply voltage at A1).
The new settings are accepted.
Connection examples
Figure 7.1: Safety monitoring device with one protective sensor with monitored start (restart interlock)
Function
Terminals
EDM selected
Monitored start: External device monitoring circuit (EDM) is connected to the start
button and terminal S35 in series relative to the starter button
Non-monitored start: External device monitoring circuit (EDM) is connected to the
start button and terminal S34 in series relative to the starter button
Automatic start: External device monitoring circuit (EDM) is connected to terminals
S33 and S34 in place of the bridge for automatic start