PROFINET interface
67
AMS 348
i
Leuze electronic
9.9.3.16 Module 1: Position value
PROFINET module identifier
Module-ID 1001
Submodule-ID 1
Description
Outputs the current position value.
The parameters for sign, unit, resolution, count direction and offset remain adjustable.
Parameters
Parameter
Description
Rel.
addr.
Data
type
Value range
Default
Unit
CR to
module
metr.
Inch
Sign
Output mode of the sign.
Sign affects position and velocity output.
0.0
Bit
0: two's complement
1: sign + quantity
0
–
–
Measure-
ment unit
Selection of the measurement unit
1)
.
The parameter applies to all values with
measurement units. The parameter
applies to all interfaces.
0.1
Bit
0: metric
1: inch (in)
0
–
–
Resolution
Resolution of the position value.
Affects only the PROFINET output. The
resolution does not apply to:
-
Static preset
-
Dynamic preset
-
Offset
0.2
…
0.4
Bit
001 = 1: 0.001
010 = 2: 0.01
011 = 3: 0.1
100 = 4: 1
101 = 5: 10
110 = 6: free resolution
4
mm
in/100
20a
Count direc-
tion
Counting direction positive:
Counting direction negative:
The parameter applies to all interfaces.
The count direction changes the sign
during velocity measurement.
0.5
Bit
0: positive
1: negative
0
–
–
Offset
Output value = measurement
value+offset.
The parameter applies to all interfaces.
Attention
:
If the preset is activated, it has priority
over the offset. Preset and offset are not
offset against each other.
The resolution of the offset value is
independent of the resolution selected in
module 1.
The entered offset applies immediately
without any further release.
1 - 4
sign
32 bit
-999999 … +999999
0
mm
in/100
–
Parameter length: 6 bytes
1)
see following notice!
a
b
c
d
0m
+100m
0m
-100m
e