PROFINET interface
Leuze electronic
AMS 348
i
52
TNT
35/7-2
4
V
9.5
PROFINET – General information on wiring
A Cat. 5 Ethernet cable should be used for wiring.
For the connection technology transition from M12 to RJ45, a "KDS
ET
M12
/
RJ 45 W - 4P" adapter is available that lets you connect standard network cables.
If no standard network cables are to be used (e.g. due to lacking IP… protection class), you
can use the "KB ET - … - SA" ready-made cable on the AMS 348
i
sory ready-made cables for PROFINET" on page 100.
The individual AMS 348
i
devices in a linear topology are connected with the "KB ET - … -
SSA" cable, see table 11.4.5 "Accessory ready-made cables for PROFINET" on page 100.
For unavailable cable lengths, you can configure your cables yourself. For this purpose,
Leuze electronic offers a D-coded M 12 round plug connector for Bus IN and Bus Out, see
table 11.4.3 "Accessory M 12 connector" on page 98.
9.6
PROFINET – Cable lengths and shielding
Observe the following maximum cable lengths and shielding types:
Table 9.2:
Cable lengths and shielding
Connection
Interface
Max. cable length
Shielding
AMS – host
PROFINET-RT
100 m
Absolutely required
Network from the
first AMS to the
last AMS
PROFINET-RT
The maximum segment length
must not exceed 100 m for
100Base-TX Twisted Pair
(min. Cat. 5)
Absolutely required