BILS-10003 rev E
11
6 thru 20K battery cabinet dimensions
Allow 36” for service clearance in front and on one side of the battery cabinet. Placing cables in flexible
metal conduit will allow for movement of battery cabinet for service.
300 Wiring Instructions
There are two basic installation configurations of the Herytage UPS system. Following
is an overview of each configuration.
- Soft-wired (Line cord & receptacles)
- Hard-wired with external bypass switch
Installation of electrical wiring should be completed by a qualified electrician
.
National electrical code and applicable local codes should be followed.
301
Soft-wired installation (Line-cord and receptacle)
Installation requires a proper wall receptacle for the Herytage UPS power cord to plug
into, and installation of external bypass receptacles.
Note: External bypass receptacles provide power to your load equipment in the event
that the Herytage UPS requires maintenance.
Proper breaker sizing for the input line cord receptacle depends on the input voltage /
plug option ordered, see Table 301-1. Review the Herytage UPS input voltage on the