BILS-10003 rev E
38
603
Passwords
Note: Before programming or clearing the power quality logs you must first
program parameter # 30 (password) with the proper level password for the
parameter you are programming.
Level 1 Password
= 0877
Level 2 password =
For service personnel only – must go through Legacy Power
Conversion, Inc. service training course, or work with factory personnel to obtain. If
you need assistance call customer service at (800) 859-5711.
604
RS232 Commands
D
To display a parameter press
:
D,
Parameter #
Note: All parameters can be displayed with no password
P
To program a parameter press: D, parameter #,
P, New Value,
Enter
UP / Down keys:
Once a parameter is displayed you can use the up/down arrows to
scroll through the parameter list.
C
Used to clear or reset parameters, counters, power quality / alarm
logs, and to clear alarms.
L
Used to display Power quality / Alarm logs
–
This event log will
record: power quality events and alarms. The event log will show the Event #,
Event type, Event date, Event time. You can scroll through the events by using
the UP / Down arrow. First event shown will be most recent event. Must use
(ESC) key to back out to the System Status mode.
Escape
Used to back out of the log mode, program mode, or display mode.
Control D
This keyboard command will send complete parameter list out of RS-
232 port
Control L
This keyboard command will send complete log list out of RS-232 port