BILS-10003 rev E
5
Specifications*
Model
2kVA
1.6kW
3kVA
2.4kW
4kVA
3.2 kW
6kVA
4.8kW
8kVA
6.4kW
10kVA
8kW
16kVA
12.8kW
20kVA
16kW
AC Input
Input ACV &
circuit
breaker
requirements
– standard
hardwire
connection
120VAC
208VAC
240VAC
30A
15A
15A
30A
20A
15A
50A
30A
30A
60A
40A
40A
-
60A
50A
-
70A
60A
-
100A
90A
-
125A
110A
Line Cord
1
(optional)
120VAC
208VAC
240VAC
C
2
, I
2
, J, E
O, K, L
O, K, L
J, E
K, L
O, K, L
E
L, M
L, M
-
N, P
N, P
-
-
-
-
-
-
-
-
-
-
-
-
Input Voltage
Window
+15%, -20% of nominal VAC Input @ full load
+15%, -40% of nominal VAC Input @ 50% load
Frequency
60Hz, ± 3Hz. Adjustable window
AC Output
Output ACV
– Hardwire
120 / 208 / 240
Output Receptacles
Optional
Output waveform
Computer grade sine wave output power
Regulation
± 3% voltage regulation
Load Compatible
Guaranteed compatible with all loads for 90 days from date of purchase
Overload
150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown.
Greater than 125% the system will shutdown in 5 seconds.
Unit
Dimensions
H x W x D
(in.)
25.2 x 16.2 x 23
3
37.5 x 17.75 x 33.25
39 x 22 x 34
Weight ( lbs.)
208
3
275
3
290
3
565
3
465
530
570
665
Efficiency
87%
88%
90%
91%
93%
93%
91%
91%
Heat Loss BTU / W
816/239
1116/327
1213/355
1619/475
1645/482
2055/602
2160/632
3238/95
Noise Attenuation
120db common mode, 60db transverse (normal) mode
Isolation
Output is completely isolated from commercial power with less than 2 pf effective capacitive
coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a
separately derived power source
Surge Protection
6000 volts are suppressed to safe levels per ANSI/IEEE C62.41 – 1997 category A & B
waveforms
Operating Temperature
0
°
to 40
°
C (32
°
to 104
°
F)
Relative Humidity
0 to 95% without condensation
High altitude operation
Max. altitude 10,000 ft – de-rate 1
°
C off max operating temp. per 1000 ft. above sea level
Agency
UL 1778, cUL listed
User Interface
Keypad w/ LCD display, RS232 serial communications, dial in modem
*
Specifications may change without notice.
1
Line Cord Designators: C = 5-20P, I = L5-20P, J = L5-30P, E = 5-50P, O = 6-15P, K = L6-20P, L = L6-30P,
M = L14-30P, N = 6-50P, P = L6-50P
2
20 Amp Line Cord limits battery charger current to 4 Amps.
3
Weight and Dimensions are for UPS with standard internal runtime.