BILS-10003 rev E
9
203
Remote battery installations
If the batteries are installed in a remote location (battery room) utilize DC circuit
protection rated at 250A and 20,000A AIC rating. If the batteries must be some
distance from the UPS you may need to install larger battery cables between the
battery cabinets and the UPS. Call your customer service representative if you would
intend to use anything other than standard cable lengths.
204
Customer Supplied batteries with Legacy battery cabinet(s)
Utilize the same number, size and type of battery as offered by Legacy Power
Conversion, Inc.
Enersys NP18-12BFR (Legacy Part Number BAT-0373)
C&D Technologies UPS 12 - 140 (Legacy Part number BBAT-0065)
Enersys NP33-12 (Legacy Part number BBAT-0065)
C&D Technologies UPS 12 - 270 (Legacy Part number BBAT-0103)
C&D Technologies UPS 12 - 310 (Legacy Part number BBAT-0122)
C&D Technologies UPS12-150MR (Legacy Part number BBAT-10031)
C&D Technologies UPS12-300MR (Legacy Part number BBAT-10032)
C&D Technologies UPS12-350MR (Legacy Part number BBAT-10033)
205
Dimensions and clearance requirements
Table 1
Dimensions and Clearances
Model
Height
(In.)
Width
(In.)
Depth
(In.)
Front
Clearance
(In.)
Back
Clearance
(In.)
2kVA
1
3kVA
1
4 kVA
1
25.2
16.2
23
36
8
6 kVA
8 kVA
10 kVA
37.5
17.75
33.25
36
8
16 kVA
20 kVA
39
22
34
36
8
1
Dimensions are for UPS with standard internal runtime.