BILS-10003 rev E
35
Parameter
Sample
Value
Password
Level
Description
56 CF-Ainv-L
Varies
Level 2
Calibration Factor for DC Amps on Inverter. Value varies with unit
57 CF-Achgr-M
Varies
Level 2
Calibration Factor for Charger DC Amps. Value varies with unit
58 CF-Achgr-L
Varies
Level 2
Calibration Factor for Charger DC Amps. Value varies with unit
59 CF-ACpk-M
Varies
Level 2
Calibration Factor for Spike Volts. Value varies with unit
60 CF-ACpk-L
Varies
Level 2
Calibration Factor for Spike Volts. Value varies with unit
61 CF-Watts-M
Varies
Level 2
Calibration Factor for Watts. Value varies with unit
62 CF-Watts-L
Varies
Level 2
Calibration Factor for Watts. Value varies with unit
63 Future Use
NP*
64 Future Use
NP*
65 ITest
30
No Pass-
Word
Required
Number of days between inverter test – program to same value or a
different value to manually start test. The test result, time, and date of
the inverter test will be posted in the event log.
66 Low Batt
10.0
Level 2
Low battery shutdown voltage – See section 700 for an alarm
description. Low Battery Alarm setpoint. Value is programmed per
battery. Typical value is 010.0
67 Nom Batts
Level 2
Number of 12vdc batteries in one string – used to determine high
battery, low battery, and charger setpoints
68 Inverter Mins
Level 1
Number of minutes UPS has ran on battery power – to reset press
clear button when parameter is displayed
69 Inverter Runs
Level 1
Number of times Inverter has turned on – to reset press clear button
when parameter is displayed
70 Chgr On V
13.0
Level 2
Voltage per battery that the battery charger turns on
71 Chgr Off V
14.0
Level 2
Voltage per battery that the battery charger turns off
72 Batt Fail V
6
Level 2
Voltage per battery that causes the Battery Fail Alarm
73 Xfr Inhibit Ult
012.8
Level 2
Specialty Customer Application Only
74 Future Use
NP*
75 Alm Rly Mask1
192
Level 1
Disables or enables certain alarm from engaging dry contacts.
Alarms will still be entered into events log. See Section 703.
76 Alm Rly Mask2
255
Level 1
Disables or enables certain alarm from engaging dry contacts.
Alarms will still be entered into events log. See Section 703.
77 Alm Rly Mask3
110
Level 1
Disables or enables certain alarm from engaging dry contacts.
Alarms will still be entered into events log. See Section 703.
78 HiBat SD Time
000
Level 1
Delay time before shutdown due to High Battery Alarm.
79 DCV Maximum
112.0
Level 1
Highest recorded DC voltage since last reset
– to reset, install password, display parameter, and press clear
80 Near Low Batt
11.0
Level 2
Near Low Battery Alarm setpoint. Value is programmed per battery.
Default is 011.0
81 Brnout 0-50%
60
Level 1
Percent of nominal input voltage (parameter 18) at which the UPS will
go to inverter based on load percent of 0 – 50%.