background image

 

Tripp Lite

1111 West 35th Street

Chicago, IL 60609 USA

Telephone: +(773) 869 1234

E-mail: 

[email protected]

Model #: SM3000NAFTA

Smart Pro line interactive UPS System - NAFTA assembled version of SMART3000NET

 

Highlights

3000VA / 3kVA line interactive, extended-run tower UPS

Maintains 120V nominal output over an input range of 87 to 140V

Network communications supported via 3 DB9 ports (1 serial / 2 contact

closure)

Current monitoring and switched PDU control via 2 single-outlet load banks

Input: L5-30P (120V 30A) / Output: 4 NEMA 5-15/20R, 4 NEMA 5-15R (120V)

$250,000 

Ultimate Lifetime Insurance

 (USA, Puerto Rico and Canada only)

Description

Tripp Lite's SM3000NAFTA intelligent, line interactive large tower UPS system protects servers, networking accessories and telecommunications

equipment from blackouts, voltage fluctuations and transient surges. Large internal batteries offer 23 minutes half load runtime and 7 minutes fully

loaded. Runtime is expandable with optional BP24V28-2U (limit 1) and BP24V70-3U external battery packs. 3000VA/2400 watt power handling

capability supports a variety of networking, telecom and other sensitive electronic applications. Includes 8 protected outlets. Supports remote

monitoring of UPS and site power conditions via built-in RS-232 enabled monitoring port, plus standard UPS monitoring via 2 built in contact closure

ports. Includes PowerAlert UPS monitoring and unattended shutdown software with complete cabling. Built-in audible alarm and front panel LEDs

indicate line power, battery power, battery charge level, load level and voltage regulation status. Network grade AC surge suppression protects

equipment from damage and performance problems resulting from transient surges. Attractive large gray tower housing. $250,000 

connected

equipment insurance

.

Package Includes

SMART3000NET UPS System

PowerAlert Software and three 6 foot network cables

Warranty information

Instruction manual

Features

SM3000NAFTA line interactive UPS offers battery derived AC output during power outages, voltage regulation during brownouts and

overvoltages, plus network-grade AC surge suppression

3000VA/2400 watt power handling capability supports a variety of networking, telecom and other sensitive electronic devices

Large internal batteries offer runtimes of 23 minutes at half load (1500VA/1200 watts) and 7 minutes at full load (3000VA/2400 watts)

Runtime is further expandable with optional external BP24V28-2U (limit 1) and BP24V70-3U battery packs

Automatic Voltage Regulation (AVR) circuits maintain 120V nominal output over an input voltage range of 87-140V

Includes 8 fully protected outlets (4 NEMA 5-15R & 4 NEMA 5-15/20R) with 2 single outlet load banks that can be individually powered off

and back on again via software interface

PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification,

event logging and running user defined script commands

Offers simultaneous monitoring of up to 3 directly connected devices through included DB9 contact closure and RS-232 enabled interfaces,

or the monitoring of any number of additional servers over IP with included PowerAlert monitoring software

Summary of Contents for Smart Pro SM3000NAFTA

Page 1: ...ndicate line power battery power battery charge level load level and voltage regulation status Network grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges Attractive large gray tower housing 250 000 connected equipment insurance Package Includes SMART3000NET UPS System PowerAlert Software and three 6 foot network cables Warranty inform...

Page 2: ...e 13 5 Output voltage regulation Battery mode 5 Built in UPS output receptacles 4 5 15R outlet s 4 5 15 20R outlet s Built in controllable switched load banks Three switchable single outlet 5 15R load banks Output circuit breaker 15A branch rated x2 each breaker protects 4 outlets Basic PDU options PDU1220 1U 13 5 15 20R outlets PDUNV 1U 2 C19 12 C13 outlets PDUV20 0U 12 5 15 20R outlets PDU40TDUA...

Page 3: ...5 and 105 are boosted by 10 Severe undervoltage correction Input voltages between 87 and 94 are boosted by 22 LEDS ALARMS SWITCHES LED Indicators 5 LEDs indicate line power battery power overload voltage regulation and battery low replace status Alarms Audible alarm indicates power failure overload and low battery conditions Alarm cancel operation Power fail alarm can be silenced using alarm cance...

Page 4: ... Range 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius Storage Temperature Range 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius Relative Humidity 0 to 95 non condensing AC mode BTU hr full load 82 4 Battery mode BTU hr full load 1219 3 COMMUNICATIONS Communications interface DB9 Serial Contact closure Network monitoring port description Supports detailed monitoring of UPS and site power...

Page 5: ...70 3U BP24V70 3U External Battery Pack for UPS System 1 Power Distribution PDU1215 Basic PDU Power Distribution Unit Safe reliable power distribution for critical networking equipment 1 Power Distribution PDU1220 Basic PDU Power Distribution Unit Safe reliable power distribution for critical networking equipment 1 Power Distribution RS 1215 Tripp Lite Power Strip Multiple outlets wherever you need...

Reviews: