29
Part B MFC 081 Signal Converter - Software Version P2.20
5.
Operation of the Signal converter
5.1
Operating and check elements
The operating elements are accessible after removing the cover of the electronics section
using the special wrench. The converter is also programmable with magnetic sensors and a
bar magnet without removing the covers of the electronic housing.
Caution:
Do not damage the screw thread and the gasket, never allow dirt to accumulate,
and make sure they are well greased at all times.
MFC 081
1 Display 1st (top) line.
2 Display 2nd (middle) line.
3 Display 3rd (bottom) line,
arrows ( ) to identify the
state of the signal converter:
- Status message indicator
- Standby mode.
4 Keys for operator control of
the signal converter.
5 Magnetic sensors to set the
converter by means of a
handheld bar magnet without
opening the housing. Function
of sensors same as keys 4 .
6 Compass field, signals
actuation of a key.
The operator control concept consists of three levels (horizontal). See next page.
Setting level:
This level is divided into three main menus:
Fct. 1.0 OPERATION: This menu contains only the most
important parameters and functions of Menu 3 (install) to allow
rapid changes to be made during the measurement mode.
Fct. 2.0 TEST: Test menu for checking the signal converter
(displays, outputs, measuring range), and the primary (transducer)
operation.
Fct. 3.0 INSTALL: All flow measurement- and flowmeter-specific
parameters and functions can be set in this menu.
Parameter check level:
Fct. 4.0 PARAM.ERROR: This level is not selectable.
After exiting from the “Setting level”, the signal converter checks
new data for plausibility. If an error is detected, the signal
converter indicates PARAM.ERROR in Fct. 4.0. In this menu, all
functions can be scanned and those changed that are not
“plausible”.
Reset/acknowledge
This menu has two tasks and is selected via Entry Code 2
level (Quit):
(
↵
↑
→
)
1) Resetting of totalizer, provided that resetting is enabled under
Fct. 3.8.5 ENABL.RESET, input YES.
2) Status message and acknowledgement (Quit) messages that
have occurred since the last acknowledgement are indicated
in a list. After elimination of the cause(s) and
acknowledgement, these messages are deleted from the list.