For applicaitons where CE approval is required, the BTS 12 L cable is prepared by Krohne to
the required length, ready for installation. For non-CE applications, the cable provided may be
prepared only at the converter end to permit the customer to more easily route the cable
during installation, and tailor the length as needed. In these cases, the transducer end of the
signal cable will need to be prepared by the customer using the parts in the kit provided with
the cable. The kit contains the following items:
Connector Sleeves:
(2) - 1 mm
2
for violet and black wire ends
(6) - 0.5 mm
2
for remaining wire ends
Shrink Tubes:
(1) - 35 mm long,
φ
12 mm (A)
(2) - 15 mm long,
φ
6 mm (B)
(3) - 15 mm long,
φ
3 mm (C)
Connector sleeves are to be crimped on to the wire ends indicated and shrink tubes A, B, and
C are to be installed as shown in Figure 31. Unused conductors should be cut back cleanly to
avoid interference with the active conductors and shields.
Figure 31: Stripping lengths and shrink tube locations for BTS 12 L signal cable -
transducer end