KOZI
D
IRECT
V
ENT
G
AS
S
TOVE
14
VENTING CONFIGURATIONS:
VERTICAL TERMINATION
The shaded areas of the two diagrams below illustrate the allowable venting configuration
when installing straight vertical or offset vertical venting utilising a vertical venting
termination cap.
Figure: 7 - Illustration of allowable vertical venting configurations.
Examples:
•
Venting with vertical termination.
A 10-foot vertical rise falls within the shaded
area, and therefore is an allowable venting configuration.
•
Venting with an offset to vertical termination.
A 15-foot vertical rise with a 4-foot
horizontal offset distance falls within the shaded area and is an allowable venting
configuration.
All Vertical And Offset Vertical Vent Installations Require The Use Of The
Simpson Dura-Vent Vent Restrictor. If The Venting Is Enclosed In A Chase,
(Minimum Size Of 9” X 9”), Maintain A 1¼” Clearance To All Combustibles.
ATTENTION:
All vertical
applications must
use the HIGH WIND
TERMINAL.