3. With the pipe attached to the stove, slide the unit into its correct location
and mark the wall for a 10" x 10" square hole. The centre of the hole
should coincide with the centreline of the horizontal incorporating the
required inclination. Cut and frame the hole in the exterior wall where
the vent will be terminated.
4. Apply a thin bead of non-hardening mastic around the outer edges of the
terminal to ensure a tight seal between the Stand-off and the terminal.
Attach the Vinyl Siding Stand-off, if required, to the Horizontal Vent
Terminal. Install the vinyl siding stand-off between the vent cap and the
exterior wall and attach with the four wood screws provided. Seal around
the vinyl stand-off on all four sides. The arrow on the exterior of the vent
cap should be pointing upwards. Ensure that all clearances have been
maintained. (The four wood screws should be substituted with the
appropriate fastener particular to your buildings exterior finish.)
5. Prior to connecting the horizontal run of vent pipe to the vent terminal,
slide the decorative wall thimble cover over the pipe, and attach with
wood screws.
6. Slide the appliance and vent assembly towards the wall, carefully
inserting the vent pipe into the vent cap assembly. It is important to
insure that the vent pipe fits into the vent cap by a minimum overlap of
1-1/4 inches. Secure the connection between the vent pipe and the vent
cap by attaching the sheet metal strips extending from the vent terminal
assembly into the outer wall of the vent pipe. Use the two sheet metal
screws provided for attaching the pipe and strapping. Bend any
remaining strapping back towards the vent cap to conceal it behind the
wall thimble.
NOTE: Horizontal runs of venting must be supported every three
feet. Wall strapping kits are available for this purpose.
NOTE: The horizontal run must possess a ¼” rise per foot of run
towards the terminator. Never allow the venting to run downwards.
This situation could cause excessive temperature build up and
present the possibility of fire and safety hazards.
NOTE: The venting terminal shall never be recessed into a wall or
siding. The vinyl siding standoff kit is not mandatory on all
horizontal termination installations, only when the exterior of the
building possesses a vinyl siding finish.