Use the minimum clearances provided below with the appropriate dimension shown in Fig.
2, also below.
A.
Side Wall To Unit
10” (254 mm)
B.
Back Wall To Unit
1” (25 mm)
C.
Back Wall To Flue Centreline
5.5” (140 mm)
D.
Side Wall To Flue Centreline
21.5” (546 mm)
E.
Side Wall To Unit
1” (25 mm)
F.
Side Wall To Flue Centreline
9” (228 mm)
Figure: 4 - Minimum Clearances Diagram.
COMBUSTION AND VENTILATION AIR
VENTING
The instructions contained within the pages of this manual pertain to the installation of
Simpson Dura-Vent Direct Vent System model DV-GS
. This venting system, in
combination with the
KOZI
Direct Vent Freestanding Gas Stove, DV1
, have been tested
and listed as a direct vent space heater by Warnock Hersey.
Note:
The fresh combustion air required by this gas stove is drawn from
outside the building through the outer flue. Therefore, there is no need for extra
provisions to increase the air inside the room containing the appliance.
Minimum ceiling clearance height is 38” (965 mm) from the top of the unit.