Connecting to an
MS/TP network
Before connecting the AppStat to a BACnet MS/TP network, configure the
network properties. See the topic
for the
procedure to set the following:
Device instance
MAC address
Baud
Use the following principles when wiring the AppStat to an MS/TP network:
Connect no more than 128 addressable BACnet devices to one MS/TP
network. The devices can be any mix of AppStat controllers, other
BACnet controllers, or BACnet routers.
To prevent network traffic bottlenecks, limit the MS/TP network size to
60 controllers.
Use 18 gauge, twisted pair, shielded cable with capacitance of no more
than 51 picofarads per foot for all network wiring. Belden cable model
#82760 meets the cable requirements.
Connect the -A terminal in parallel with all other - terminals.
Connect the +B terminal in parallel with all other + terminals.
Connect the shield to an earth ground at one end only.
Use a KMD-5575 repeater between every 32 MS/TP devices or if the total
cable length will exceed 4000 feet (1220 meters). Use no more than four
repeaters per MS/TP network.
Place a KMD-5567 surge suppressor in the cable where it exits a building.
For more information on installing HVAC system controllers, see
Application
Note AN0404A, Planning BACnet Networks
.
Installation, Operation, and Application Guide for AppStat
Section 7: System integration
Revision G
121
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...