Setting the
occupancy schedule
The schedule in the AppStat controls the occupancy mode. If the schedule is
set to ON, the AppStat uses the occupied setpoint as the active setpoint. If the
schedule is OFF, the unoccupied setpoint is used.
Note:
The schedule in the AppStat is a BACnet schedule object. If the AppStat is
connected to a BACnet network the schedule can be set up with a BACnet
operator workstation.
Setting the occupancy schedule requires entering Password 2 which is
described in the topic
To change the time and date, see the procedure
Procedure
Steps
Display
1
Starting display
1.
Start at the temperature display.
2.
Enter Password 2. The display changes to the
MAIN menu display.
F
°
70
AUTO
AUTO
SECURITY
ADMIN LEVEL
0
0 0 0
2
Select the
SCHEDULE menu.
1.
From the MAIN menu , press either the
or
button to select SCHEDULE.
2.
Press
Enter
. The SCHEDULE menu opens.
MAIN
SETPOINT
SCHEDULE
SYSTEM
COMM
ADVANCED
Back
Enter
Exit
Set up schedules
Installation, Operation, and Application Guide for AppStat
Section 4: Commissioning functions
Revision G
47
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...