Procedure
Steps
Display
3
Set the local override
time.
From the SYSTEM menu choose LOCAL OVRD
TIME to set the time the AppStat will hold an
override temperature setpoint as the active
setpoint. At the end of the period, the AppStat
will use either an occupied or unoccupied
setpoint as the active setpoint.
Back
Enter
Cncl
LOCAL OVRD TIME
2 60 mins
4
Set the fan delay.
From the SYSTEM menu choose FAN DELAY
OFF to set the time the system fan will continue
to run after the last heating or cooling stage is
turned off.
Back
Enter
Cncl
FAN OFF DELAY
2 2 mins
5
Set the occupied fan
control.
From the SYSTEM menu choose OCCUPIED
FAN to choose the following:
When ON, the fan will run continuously
when the AppStat schedule is ON (occupied).
When the AppStat schedule is OFF
(Unoccupied) the fan will run only when
there is a call for heating or cooling.
Back
Enter
Cncl
OCCUPIED FAN:
ON
OFF
6
Set up staged cooling
and heating.
To set up staged cooling and heating do the
following:
1.
From the SYSTEM menu choose MIN OFF
TIME to enter the time a stage must remain
turned off before it can be turned on again.
2.
From the SYSTEM menu choose STAGE
DELAY to enter the time the first stage must
remain turned on before the second stage
can be turned on.
Back
Enter
Cncl
MINOFF TIME:
5 mins
Back
Enter
Cncl
STAGE DELAY:
10 mins
Set up heat pump unit system options (continued)
Installation, Operation, and Application Guide for AppStat
Section 4: Commissioning functions
Revision G
57
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...