Enter the
commissioning
mode
For access to the commissioning functions you will need to know Password 2.
If the controller has not been previously set up, no password is required.
A new Password 2 can be entered in the advanced commissioning
functions. See the topic
.
Procedure
Steps
Display
1
Starting display
Start from the temperature display.
F
°
70
AUTO
AUTO
2
Enter the
commissioning
password
1.
Press the left and right buttons below the
display at the same time and hold them until
the display changes to the SECURITY USER
LEVEL display.
Note:
If Password 2 has not previously been
entered, the display will change to the
MAIN menu.
2.
Press either the
or
button to change the
first digit of Password 2.
3.
Press the
Enter
button to select the next
digit. Repeat for all four digits. The Enter
button is the middle of the three buttons
below the display.
Push together for
commissioning
AUTO
AUTO
70
F
°
SECURITY
ADMIN LEVEL
0
0 0 0
3
Select a
commissioning
function
Access to the commissioning functions always
starts at the MAIN menu display.
Enter
Cncl
MAIN
SETPOINT
SCHEDULE
SYSTEM
COMM
ADVANCED
Enter the commissioning mode
Section 4: Commissioning functions
KMC Controls, Inc.
40
Revision G
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...