Roof Top Unit
applications
This section covers applications for roof top units. For other applications see
and
.
Roof Top Unit—Two-stage gas heat and two-stage DX cooling
This application applies to models BAC-4221CW0002, BAC-4021CW0002,
BAC-4201CW0002, and BAC-4001CW0002.
Fan status switch (FST) and discarge air temperature (DAT) and outdoor
air temperature (OAT) sensors are optional. They are typically used only
when the AppStat is connected to a network.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
For single stage heating, delete connection W2.
For single stage cooling, delete connection Y2.
Connect outputs to 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see
.
For additional detail on connecting the fan and valves, see
.
KMC Part
No.
Description
Function
CSE-1102
Differential Pressure Switch, Barb Fittings
Fan status switch
STE-1405
Duct temperature sensor, 10 kΩ Type III
Discharge air temperature
STE-1451
Outdoor air temperature sensor, 10 kΩ Type III
Outdoor air temperature
STE-6011W10
Temperature sensor, 10 kΩ Type II
Remote space temperature
XEE-6111-040
XEE-6112-040
XEE-6311-075
Single-hub 120 volt power transformer
Dual-hub 120 volt power transformer
120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
Table 6–11 Materials list
Section 6: Application drawings
KMC Controls, Inc.
98
Revision G
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...