Temperature points
—The following analog value objects represent
temperatures points derived from the AppStat input sensors.
Value object
Name
Description
AV1
SPACE_TEMP
Space Temperature
AV19
OUTDOOR_TEMP
Outdoor Air Temperature
AV20
DISCHARGE_TEMP
Discharge Air Temp
AV21
REL_HUMIDITY
Relative Humidity
Table 7–7
Analog value objects—Temperature points
Economizer and heat pump unit setpoints
—The following analog value
objects represent setpoints for AppStat heat pump unit and economizer
operation.
Value
object
Name
Description
AV13
DAT_RESET
Discharge Air Reset STPT
AV14
MIN DAT
Min Discharge Air Temp
AV15
MIN_ECON_DAMPER Minimum Econ Damper
AV16
ECON_ENABLE_
TEMP
Economizer Enable Temperature
AV17
CMP_LOCKOUT
Compressor Lockout
Temperature
AV18
AUX_HT_LOCKOUT
OAT AUX Heat Lockout
Table 7–8
Analog value objects—Economizer and HPU setpoints
Operating states and modes
—The binary and multistate value objects
represent operating conditions in the AppStat. Objects BV5 and BV36 are
releated to the schedule.
Value object
Name
Description
BV5
OCC_SCHEDULE
Occupy Schedule
BV13
OCCUPIED_FAN
Fan On During Occupied Mode
Table 7–9
Binary value objects
Section 7: System integration
KMC Controls, Inc.
118
Revision G
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...