Procedure
Steps
Display
15
Reset the
application and
choose units of
measure.
Choose RESTORE APP from the ADVANCED
menu to reset the AppStat to the original
configuration and settings. Use it also to change
the AppStat application program and the units of
measure to display. There are two versions of
each application program in every AppStat.
The Metric version displays temperature in
Celsius and uses metric values for units of
measure.
The English version displays temperature in
Fahrenheit and uses English values for units
of measure.
Note:
Choosing an application will reset the
AppStat.
RESTORE APP
2P FCU-METRIC
4P FCU-METRIC
2P FCU-ENGLISH
4P FCU-ENGLISH
Back
Enter
Cncl
RESTORE APP
RTU-METRIC
RTU-ENGLISH
Back
Enter
Cncl
RESTORE APP
HPU-METRIC
HPU-ENGLISH
Back
Enter
Cncl
16
Adjust the PID
loops.
Choose LOOPS from the ADVANCED menu to
adjust the values for the cooling or heating PID
loops. Only the proportional and integral
properties can be changed from the display.
The proportional default is 2° F.
The integral default is zero (0).
LOOPS
COOL PROP
COOL INTG
HEAT PROP
HEAT INTG
Back
Enter
Exit
Choosing advance options (continued)
Installation, Operation, and Application Guide for AppStat
Section 4: Commissioning functions
Revision G
61
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...