Procedure
Steps
Display
17
Enter or change
passwords.
Choose PASSWORDS from the ADVANCED
menu to set either Password 1 or Password 2.
Password 1 is for a facility user and limits
changes to active setpoints, fan operation,
occupancy, and heating and cooling modes.
Password 2 is for a controls technician to set
up and commission the AppStat.
Note:
Entering four zeros (0000) removes the
password. The AppStat is supplied without
passwords.
1.
From the PASSWORD1 or PASSWORD2 menu
press either the
or
buttons to change the
first digit of the password.
2.
Press the
Enter
button to select the next digit.
Repeat for all four digits.
3.
When the Enter button is pressed for the last
digit, the new password is saved and the
display advances.
PASSWORDS
PASSWORD1
PASSWORD2
Back
Enter
Exit
PASSWORD1:
0
0 0 0
Del
Enter
Cncl
18
Calibrate the
inputs.
Choose CALIBRATION from the ADVANCED
menu to calibrated an input. The AppStat
includes two calibration entries; one for the
internal temperature sensor and one for the
optional remote temperature sensor connected to
the RS terminal.
Enter a calibration factor to adjust either input
for sensor inaccuracies.
For a low input reading enter a positive
correction value.
For a high input reading enter a negative
correction value.
CALIBRATION
CAL INTERNAL
CAL EXTERNAL
Back
Enter
Exit
CAL INTERNAL:
0.0
Back
Enter
Cncl
Choosing advance options (continued)
Section 4: Commissioning functions
KMC Controls, Inc.
62
Revision G
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...