Roof top unit—Cooling and heating with modulating valves and
economizer
This application applies to models BAC-4003CW0002, BAC-4023CW0002,
BAC-4203CW0002, and BAC-4223CW0002.
Fan status switch (FST) is optional. Typically it is used only when the
AppStat is connected to a network.
Discharge air temperature (DAT) and outdoor air temperature (OAT)
sensors are required for economizer operation.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
Connect the fan output to a 24 volt AC pilot duty input.
For additional details on connecting sensors, see
.
For additional details on connecting the fan and valves, see
.
KMC Part
No.
Description
Function
CSE-1102
Differential Pressure Switch, Barb Fittings
Fan status switch
STE-1405
Duct temperature sensor, 10 kΩ Type III
Discharge air temperature
STE-1451
Outdoor air temperature sensor, 10 kΩ Type III
Outdoor air temperature
STE-6011W10
Temperature sensor, 10 kΩ Type II
Remote space temperature
XEE-6111-040
XEE-6112-040
XEE-6311-075
Single-hub 120 volt power transformer
Dual-hub 120 volt power transformer
120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
Table 6–13 Materials list
Section 6: Application drawings
KMC Controls, Inc.
102
Revision G
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...