Set up
communications
Setting BACnet communications properties is required only if the AppStat is
integrated into a network with other BACnet controllers. Entering the
communications properties requires entering Password 2 which is described
in the topic
See the topic
Connecting to an MS/TP network
for network
wiring details.
Procedure
Steps
Display
1
Starting display
1.
Start at the temperature display.
2.
Enter Password 2. The display changes to the
MAIN menu display.
F
°
70
AUTO
AUTO
SECURITY
ADMIN LEVEL
0
0 0 0
2
Change the network
communication
properties.
1.
From the MAIN menu , press either the
or
button to select COMM.
2.
Press
Enter
. The COMM menu opens.
3.
Choose and set the following properties.
l
DEVICE ID—This is the BACnet device
instance. The device instance must be
within the range of 1 to 4,194,302.
l
MAC—The MAC address must be in the
range of 1-127.
l
BAUD—Set to match other devices on
the BACnet MS/TP network. The choices
are Auto, 9600, 19,200, 38,400, or 76,800.
Note:
After changing a communication
property the AppStat will reset.
MAIN
SETPOINT
SCHEDULE
SYSTEM
COMM
ADVANCED
Back
Enter
Exit
COMM
DEVICE ID
MAC
BAUD
Back
Enter
Exit
D ID:
0
000001
Done
Enter
Enter
Set BACnet communication properties
Installation, Operation, and Application Guide for AppStat
Section 4: Commissioning functions
Revision G
43
Содержание BAC-4000 series
Страница 6: ...Contents KMC Controls Inc 6 Revision G ...
Страница 30: ...Section 2 Installing the AppStat KMC Controls Inc 30 Revision G ...
Страница 64: ...Section 4 Commissioning functions KMC Controls Inc 64 Revision G ...
Страница 112: ...Section 6 Application drawings KMC Controls Inc 112 Revision G ...
Страница 124: ...Section 7 System integration KMC Controls Inc 124 Revision G ...
Страница 128: ...power 28 roof top unit 98 rough in 18 Index KMC Controls Inc 128 Revision G ...