13. Appendix
1. Cable Selections
【
Note
】
Select the cable size based on the permissible current and distance between genset
and load.If the current going through the cable exceeds the permissible current, it
may burn the cables due to overheat. If the power cable is too long, and cable size is
too small, the resistance will be large and cause a voltage drop which may stop the
load from working.
●
Choose the cable length and section area within 5% rated voltage.
●
The following formula can be used to calculate the voltage drop value "e" from
cable length,sectional area and current in 3-phase 3-line situation.
The selection chart for single core and multi-core cables is as follows: (It’s applicable
for 220V voltage with a voltage drop of less than 10V).
For rubber insulated single core cable:
Length
Current
Within
50m
75m
100m
125m
150m
200m
50A
8
14
22
22
30
38
100A
22
30
38
50
50
60
200A
60
60
60
80
100
125
300A
100
100
100
125
150
200
For rubber insulated multi-core cable: mm
2
Length
Current
Within
50m
75m
100m
125m
150m
200m
50A
14
14
22
22
30
38
100A
38
38
38
50
50
60
200A
38×2 core
38×2 core
38×2 core
50×2 core
50×2 core
50×2 core
300A
60×2 core
60×2 core
60×2 core
60×2 core
80×2 core
100×2 core
Содержание Sinemaster IG2000i
Страница 1: ...1...
Страница 8: ...7 3 COMPONENT IDENTIFICATION...
Страница 27: ...26...
Страница 46: ...45 13 WIRING DIAGRAM IG2000i Wiring Diagram...
Страница 51: ...50 Intake System and Carburetor Exhaust System...
Страница 53: ......
Страница 54: ......
Страница 60: ...4 2 COMPONENT IDENTIFICATION 2 1 Outline drawing Figure 1 Figure 1 Outline drawing...
Страница 61: ...5 2 2 Inlet System Figure 2 2 3 CARB Evaporative Control System Figure 3...
Страница 62: ...6 2 4 Carbon Canister Location CARB only Figure 4 2 5 Control panel See figure 5 Figure 5...
Страница 85: ...29 Appliance does not operate...
Страница 87: ...31 11 Electrical principle diagram Figure 32 Electrical principle diagram...