34
2. Power Derating
Test conditions: Altitude: <=1000m Ambient temperature: 5
℃
~25
℃
Relative humidity: 30%
Power derating factor: C
(
Relative humidity:30%
)
Altitude
(
m
)
Ambient temperature
(
℃
)
25
30
35
40
45
1000
1
0.97
0.94
0.91
0.87
2000
0.87
0.84
0.81
0.78
0.74
3000
0.73
0.7
0.67
0.64
0.60
4000
0.60
0.57
0.54
0.51
0.47
Note:
The power derating factor is C-0.01 @ 60% relative humidity
The power derating factor is C-0.02 @ 80% relative humidity
The power derating factor is C-0.03 @ 90% relative humidity
The power derating factor is C-0.04 @ 100% relative humidity
For example:
The rated power of the genset is 20kW (PN) in test conditions. To determine the
power if the altitude is 2000 meters, the ambient temperature 40
and the relative
℃
humidity is 80%:
P=PN×(C-0.02)=20×(0.78-0.02)=15.2KW