PFX2512_CE
23
Connecting the Power Cord
2
In
st
al
la
ti
on
a
n
d P
re
p
ar
a
ti
o
n
4
To ensure the safety charge and discharge testing, the power cord of the all
connected equipments should be connected to the outlet with the same
ground terminal.
Protect the malfunction in such case when the AC power line is shut down.
Connection to the switch board
To ensure the safety charge and discharge testing, the AC power line connected with other
equipments should be wired to the same AC power line.
■
Circuit breaker of switchboard requirement
•
Rated current: 30 A (The circuit breaker of which the rated current is more than 30 A is
disabled for safety.)
•
The breaker of the switch board should be assigned exclusively for the equipment used in the
system.
•
Keep the switchboard easily accessible at any time.
•
It is required to indicate that the breaker is used exclusively for the equipment of the system
and it separates the AC power supply line.
PFX2512
DC Power Supply
Example properly ground power outlet for use
Electronic Load
Connect the power cord
of each equipment to a
properly ground power
outlet.
WARNING
Possible electric shock.
• Turn off the circuit breaker of switchboard before connecting the cord.
Possible Fire.
• Have a qualified engineer connect the power cord to the switchboard.
• The breaker of switchboard is required to meet following requirement.
CAUTION
Inside the product, protective circuits including input fuses are connected to match the polarity of
the input terminal. Make sure the colors of the wires connected to the corresponding input
terminals (L, N, and
(GND)) are correct.
Turn off the circuit breaker of switchboard to disconnect the PWR from the AC line in an
emergency.
N
L
N
L
Connection to the switchboard
(PWR1600L example)
PWR1600L
30 A
Breaker indication example
PWR1600L
Breaker dedicated
to the PWR1600L
Switchboard
Содержание PFX2515
Страница 10: ...10 PFX2512_CE This page is intentionally blank ...
Страница 11: ...General Description This chapter describes the outline of product the connectable equipments and the options ...
Страница 58: ...58 PFX2512_CE This page is intentionally blank ...
Страница 59: ...Specification This chapter contains the PFX2512 specifications and outline drawings ...
Страница 86: ...86 PFX2512_CE This page is intentionally blank ...
Страница 100: ...100 PFX2512_CE This page is intentionally blank ...
Страница 103: ......