Calibrating the device
V1.03
38
© KEBA
5) Switch on the supply voltage of the charging station.
Test mode is deactivated.
6.4
Applying the calibration stamp and seal
Calibration stamp
The calibration stamp must be affixed so that it is clearly visible at the bottom
right of the front part.
1
... Calibration stamp
Calibration seal
If a calibration seal is needed as additional protection for the meter seal
(manufacturer seal), it must be applied on one of the positions marked be-
low. The calibration seal must be applied on the left or right bottom corner
between the front part
1
and the lower unit
2
with the housing cover re-
moved.