KC-P30 Charging Station
Calibrating the device
V1.03
32
© KEBA
6
Calibrating the device
6.1
Calibration
After module B and module D, the device is assessed for conformity in ac-
cordance with
MessEG in compliance with calibration law. The manufacturer puts the de-
vice on the market in compliance with calibration law.
The charging station must be calibrated exclusively by a specifically autho-
rized institution. Calibration may only be performed on a charging station
with an intact meter seal on the front part. This seal also must not be re-
moved during or after calibration.
A calibration seal and stamp are placed as described in Chapter
ing the calibration stamp and seal
after a complete calibration.
Maintenance
The device is maintenance free. The applicable periods for the validity of cal-
ibration must be observed. Compliance with the points listed under
must be guaranteed over the entire service life.
6.2
Inspection of commissioned devices
In this section, the tests are described that must be performed as part of the
inspection of commissioned devices. All tests must be performed for each
charge point.
The tests described here depict a permitted procedure. Analogous alterna-
tives may be permitted at the discretion of the parties performing the inspec-
tions.
Essentially, the tests include the following categories:
●
Condition inspections
●
Functional tests, including accuracy checks
●
Billing control
6.2.1
Condition inspection
The charging station must be tested for agreement with the type examination
certificate:
●
Physical structure of the charging station
●
Meter and auxiliary module used
●
Type plate inscriptions
●
Stamps/seals