69
DESCRIPTION Of THE TERMINALS
6.3.5 Ethernet interface (X6b)
The standardized 10/100 base-T interface supports the protocols TCP/IP and UDP/IP.
The following ports have the functions:
The run-time system uses ports 1740-1743 for the connection to the outside. The pa-
rameters of the firmware are available via port 8001. TCP or UDP is possible as proto
-
col, at which encapsulated DIN66019II data telegrams will be transferred (the control
unit has the node address 0, the drive unit has the node address 1). The file system can
be read/written via port 8002 (only UDP) with KEB FTP file transfer protocol (writing only
with application password). Furthermore, other ports of this interface can be accessed
via the IEC control program. The interface supports automatic polarity detection, Auto-
Crossover and automatic speed detection, adjustable by parameter Et15.
Connection to programming system !
A correct adjustment is important for the programming system connection.
The IP address can be set by parameter Et01. The subnet mask is set by
parameter Et11.
Default:
IP-Address 192.168.0.100
Subnet mask 255.255.255.0
NOTICE
Protect COMbIVERT against unauthorized access !
Each user within a network can take access to the control with knowledge
of the IP address. The write access via port 8001 can be restricted by
parameter Et09.
Содержание COMBIVERT P6
Страница 2: ......