5.9 Connection of batteries / ultracapacitors
Terminal block X1b
BT+
BT-
BTM
+
+
+
+
F6
F7
18/19P6
BT+
BT-
BTM0...BTM5
+
+
+
+
F6
F7
23P6
Name
function
BT+
DC input / output for the connection of ultracapacitors/rechargeable
batteries for emergency operation. Control of charging current and
voltage ist integrated in the device; monitoring by software.
BT-
BTM (18 /19 P6)
Additional input for DC voltage measurement against BT-.
Measuring range: 0…500 V (
Ri
= 500 kΩ)
Resolution: 10 Bit
(evaluation in customer PLC program)
BTM0...BTM5
(23 P6)
6 additional inputs for DC voltage measurement against BT-.
Measuring range: 0…500 V (
Ri
= 1000 kΩ)
Resolution: 10 Bit
(evaluation in customer PLC program)
F6, F7
Fuses recommended to protect energy storage and cabling.
Figure 33: Connection of energy storages
NOTICE
Damage at the switchgear
There is no internal inrush current limiting at terminals BT+ and BT-.
Therefore, energy storages should only be connected if they are di-
scharged. Instructions for switchgear use at these terminals and for the
recommended switching sequence on request at KEB. Non-observan-
ce may lead to damage of the switchgear.