3 Technical Data
3.1 Operating conditions
3.1.1 Climatic ambient conditions
Storage
Standard
Class Descriptions
Ambient temperature
1K4
Extended to -40°C…70°C
Relative humidity
1K3
5…95 % (without condensation)
Storage altitude
–
–
Max. 3000 m above sea level
Transport
Standard
Class Descriptions
Ambient temperature
2K3
Extended to -40°C…70°C
Relative humidity
2K3
Maximum 95 % at 40 °C (without condensation)
Operation
Standard
Class Descriptions
Ambient temperature
3K3
Place
18P6
19P6
23P6
At the
heat sink
-30…60 °C -30…55 °C -30…50 °C
In the cabinet -30…70 °C -30…65 °C -30…60 °C
Relative humidity
3K3
5…85 % (without condensation)
Protection degree
IP20
Inner part (cabinet side)
Protection against foreign material > ø12.5 mm
No protection against water
Non-conductive pollution, occasional conden-
sation when PDS is out of service.
IP54
Through panel mounted heat sink side
Protection against interior dust deposits
Complete touch protection
Protected against spray water
Site altitude
–
–
Max. 3000 m above sea level
• With site altitude above 1000 m a current
derating of 1 % per 100 m must be taken into
account.
Table 2:
Climatic ambient conditions