DESCRIPTION Of THE INDICATORS AND CONTROLS
6.1.1 LEDs for program run and error display
Description
function
LED1 Fieldbus status
Off
Fieldbus driver is not activated in the PLC program;
PLC program stopped or not available;
fieldbus interface other than CAN equipped
Flashing (2.5 Hz)
CAN node status = pre-operational
On
CAN node status = operational
LED2 PLC Error
Off
Program OK or PLC program not available
On
Program error, exact error cause can be determined via
COMBIVIS.
This LED can also be controlled customer-specific by the
PLC program.
Fast flashing
Hardware error, PLC must be restarted
LED3 PLC Run
Off
PLC program stopped or not available
On
PLC program in run mode
LED4 Inverter status
Off
Drive controller part defective or no program
On
OK (24 V control voltage available)
Flashing (1 Hz)
Error in the drive controller part.Exact error cause can
be determined via COMBIVIS.
Table 12: Function of the LED's LD1…LD4
6.1.2 Address selector switch S1
The function is defined in the customer PLC program.
6.1.3 Real-time clock
The installed clock is maintenance-free (no battery) and runs without voltage supply for
about 30 days. Then it must be set again. A readable parameter displays the validity
of the date and time. For complete charging the control shall remain switched on for at
least 30 minutes. Leap years are automatically recognized until 2099. Date and time can
be read and set via COMBIVIS or the control program (library "SysTime").