POWER UNIT
5.6 Mains connection
Terminal block X1A
2
1
4
3
6
5
P6
F1...F3
L3 PE
L2
L1
L3
L2
L1
Q1
DR
Name
function
L1, L2, L3
Mains input 3-phase 400 V
F1...F3
Mains fuses
Q1
Mains switch or mains contactor (depending on application)
DR
Mains choke (recommended)
[required for "functional safety" and size 23]
PE,
Protective earth
Figure 26: Mains connection
For 18/19P6, the use of a mains choke is recommended. If using functional
safety of the P6 in the application (safety run with PL d according to
) a mains choke (e.g. 13Z1B04-1000…19Z1B04-1000) is required.
For 23P6, a mains choke (e.g. 16Z1B04-1000...21Z1B04-1000) is required.