![KEB COMBIVERT P6 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/keb/combivert-p6/combivert-p6_instructions-for-use-manual_660395062.webp)
62
DESCRIPTION Of THE TERMINALS
6.3.1.1 External supply of the control board
Using the external supply, the control board, I/Os, fieldbus, sensors (temperatures, hu
-
midity, mounting orientation) and the interior fan (of 18/19P6) remain in operation even
if the power unit is disconnected.
U
in
0Vin
U
Terminals
Specification
X2A.35
0Vin
U
in
: 24 V ±10 %
X2A.36
Uin
Others
Current consumption:
Own use 0.65 A
+ load currents at DO 0 ... DO 8
+ load currents at X2B.1/3 ... 31
+ load currents at X3A and X3B
Figure 39: External supply of the control board
6.3.1.2 Digital outputs
All outputs are short-circuit proof. They are suitable for inductive loads (without free-wheel-
ing diode up to 300 mJ max.). The sum of the load currents at the 24 V outputs of the
control card (DO 0...DO 8, X2B.1/3...31 and X3A und X3B) must not exceed 3.4 A.
DO 0...7
0V
I
L_max
Terminals
Specification
X2A.18/20…32 DO 0…7
U
dc
: 24 V
X2A.17/19…31 0 V
I
L_max
: 250 mA
Figure 40: Digital outputsDO 0…DO 7
DO 8
0V
I
L_max
Terminals
Specification
X2A.34
DO 8
U
dc
: 24 V
X2A.33
0 V
I
L_max
: 2 A
Figure 41: Digital output DO 8
Содержание COMBIVERT P6