CERTIfICATION
8
Certification
8.1 CE Marking
CE marked drive controllers were developed and manufactured to comply with the reg-
ulations of the Low-Voltage Directive and EMC directive. The harmonized standards of
and
8.2
UL certification
Not planned for 18/19P6.
For 23P6 only:
Acceptance according to UL is marked at KEB drive controllers with
the adjacent logo on the nameplate.
To be conform according to UL for use on the North American and Canadian Market the
following additional instructions must be observed (English original text):
Special Considerations
•
The product was evaluated for use in and under the provisions for installation in a
Pollution Degree 2 and Overvoltage Category III environment.
•
The product is not intended for use in corner-grounded delta systems, the phase-
to-ground rated system voltage is 277V AC or 230V AC respectively.
•
All wiring terminals are suitable for field wiring.
•
These devices also comply with IEC 61800-5-1.
Use – When installed in the final use equipment, the following are among the consid
-
erations to be made:
•
Short Circuit and Breakdown of Component testing was conducted in normal
mode and stored energy mode with the following external ultracapacitor modules
and external fuses:
Part
Manufacturer
Type
Cat. No.
Min./Max.
Capacitance
Max.
Voltage
Ultra
Capacitors
Maxwell
BBBG2.MH26456
160V 6F Module BMOD0006
E160 C02
6.0
(50k cycles)
162Vdc per
Module
Fuses
MERSEN
JFHR2/8.E76491
50A, 500Vdc
IR 50kAdc
FR14GR69
V50T
N/A
500Vdc
12 of the above modules were used in serial connection of 3 modules, 4 of such
series connections in parallel, for Udc=480V.
Any other external ultracapacitor modules and/or external fuses shall be judged in
the end use.
•
The need for disconnecting means of the drive from the ultracapacitor supply for
service and testing shall be determined in the end use. This means shall open all
ungrounded conductors, be rated for the voltage and current involved, and have
a short-circuit current rating equal to or greater than the maximum available fault
current from the ultracapacitors.
•
A suitable enclosure shall be provided in the end-product application.