19
bASIC SAfETy INSTRUCTIONS
CAUTION
High temperatures on the heat sink!
burning of the skin!
►
Cover hot surfaces safe-to-touch.
►
If necessary, attach warning signs on the system.
►
Check surface before touching.
►
Before any working let the unit cool down.
• During operation, all covers and doors shall be kept closed.
• Use only approved accessories for this device.
• Never touch terminals, busbars or cable ends.
If a P6 drive controller has not been in operation for more
than a year, observe the following information.
www.keb.de/fileadmin/media/Techinfo/dr/tn/ti_dr_tn-format-capaci
1.4.3 Insulation measurement
An insulation measurement (according to
chapter 18.3) with DC 500 V is
permitted if all connections in the power section (grid-connected potential) are bridged
with each other and all control connections are bridged with PE.The insulation resist-
ance of each product can be found in the technical data.
1.5 Start-up and operation
The drive controller must not be started until it is determined that the installation com-
plies with the machine directive; Account is to be taken of
.
WARNING
Software protection and programming !
Hazards caused by unintentional behavior of the drive!
►
Check especially during initial start-up or replacement of the drive
controller if parameterization is compatible to application.
►
Securing a unit solely with software-supported functions is not suf-
ficient. It is imperative to install external protective measures (e.g.
limit switch) that are independent of the drive controller.
►
Secure motors against automatic restart.
Содержание COMBIVERT P6