GB - 8
2.3
Technical data
2.3.1 230 V class
Product description
Inverter size
09
10
Housing size
B
Phases
1
3
1
3
Output rated power
[kVA]
2.8
4.0
Max. rated motor power
[kW]
1.5
2.2
Output rated current
[A]
7.0
10
Max. short time current
[A]
12.6
18
OC-tripping current
[A]
15.1
21
Input rated current
[A ] 14
9.8
20
14
Max. permissible mains fuse (inert)
[A] 20
16
25
20
Rated switching frequency
[kHz]
4
4
Max. switching frequency
[kHz]
8
8
Power loss at nominal operating
[W]
59
85
Input rated voltage
[V AC]
230 (UL:200…240)
Input voltage range U
mains
[V AC]
180…264 ±0
Mains forms
TN, TT, IT
2)
, Delta
3)
Mains frequency
[Hz]
50…60 ±2
Output voltage
[V]
3 x 0…U
mains
Output frequency
[Hz]
0…400
Min. motor line cross section
[mm
2
]
1.5
2.5
Max. motor line length (shielded)
[m] 30 at limit value class C2
10 at limit value class C1
With intergrated braking transistor
Typically braking resistor
[Ω]
100
68
Maximal braking current
[A]
9.5
12
Leakage current with internal filter (at nOP)
[mA]
6
2) insulating resistance at mains form IT = 2 MΩ
3) on inquiry
Site altitude maximal 2000 m above sea level. With site altitudes over 1000 m a derating of
1 % per 100 m must be taken into consideration.