3.6
Monitoring during Operation
The WTC 1600 is monitored by an SPS (storage programmable control)
system. If a fault occurs it is indicated on the operating panel (49/7) and
the lamp "Fault reset" (49/9) illuminates on the switch cabinet.
Correct the fault according to Section 4.1. Then press the "Fault reset"
button (49/9) on the switch cabinet.
To avoid faults occurring, the following checks are to be carried out
every
20 operating hours or 1x daily
:
Preliminary Filter
Selector Switch
1.
If the difference in pressure between the preliminary filter inlet
and outlet becomes too high, the system automatically switches
over to the redundant filter.
➜
On the operating panel (49/7) "Renew filter bag F02 (or F03)" is
indicated
➜
Lamp (49/6) for the switched-off filter bag flashes
2.
Change the filter bag according to Section 4.3.3.
3.
Press luminous lamp "Fault reset" (49/9).
➜
Lamp goes out
➜
Fault signal on the operating panel goes out
Operating Record
The following values are to be entered into the operating record:
From the SPC:
Prefilter intake pressure, main module intake pressure, intake pres-
sure of the membranes, outlet pressure of the membranes, prefilter
differential pressure, operating hours.
At the switch cabinet, respectively from the standard indication of
the SPC:
Drinking water temperature, drinking water conductivity, drinking wa-
ter flow.
UV Irradiator Function
(Option)
• Visually check the LED indica-
tion at the UV switch cabinet.
➜
Green "Function o.k." LED
(45/1) illuminated
1
Fig. 45
LED indicator
Содержание WATERCLEAN 1600
Страница 2: ......
Страница 14: ...GENERAL Version 03 2008 WATERCLEAN 1600 8 ...
Страница 28: ...DESCRIPTION Version 03 2008 WATERCLEAN 1600 22 Fig 13 Anti scalant mounting kit 1 2 ...
Страница 48: ...DESCRIPTION Version 03 2008 WATERCLEAN 1600 42 ...
Страница 82: ...OPERATION Version 03 2008 WATERCLEAN 1600 76 ...
Страница 106: ...APPENDIX Version 03 2008 WATERCLEAN 1600 100 ...
Страница 108: ......
Страница 110: ......