OPERATION
Version 03/2008
WATERCLEAN 1600
- 60 -
3.4.3.1
Switching ON in Manual Operation Mode
DANGER
When putting into operation for the first time, after disin-
fecting, cleaning, preserving or applying anti-freeze,
reject the drinking water for at least 30 minutes and after
the system has stood still for between 24 - 60 hours,
reject for 15 minutes.
1.
Set main switch (49/16) to position
I
"ON".
➜
Same reactions as in Section 3.4.2.1 "Switching on in Auto-
matic Operation Mode"
2.
Turn "Program" selector switch (49/12) to position
1
"Manual".
3.
Press luminous "Start" button (49/11).
➜
On the operating panel display (49/7) "Manual" is indicated
and then "Pass 1"
➜
"Raw water pump ON" lamp (49/13) illuminates
WARNING
In manual operation mode the level sensors of the
drinking water interim storage are not active. Dan-
ger of overfilling of the tank. Water level has to
checked by operator.
Adjustment Procedure
In order to adjust the system to the operating point, it is necessary to
switch back and forward several times between the menus "Pass 1"
and "Pass 2" so that the specified flow rate values can be adjust or cor-
rected.
Setting values:
WARNING
The reference value for Pass 1 is always 1 000 l/h.
The reference value for 2 is 20 bar of pressure or a
flow rate of 600 l/h max.
NOTE
In most cases, the maximum pressure of 20 bar is
reached as the limit in Pass 2. A further increase of
the pressure / flow rate is then no longer possible
• Step 1: Pass 1 to 600 l/h
• Step 2: Pass 2 to 100 l/h
• Step 3: Pass 1 to 1 000 l/h
• Step 4: Pass 2 to 200 l/h
• Step 5: Pass 1 to 1 000 l/h
• Step 6: Pass 2 to 250 l/h
• Step 7: Pass 1 to 1 000 l/h
• Step 8: Pass 2 to 300 l/h
• Step 9: Pass 1 to 1 000 l/h
• Step 10: Pass 2 to 350 l/h
• Step 11: Pass 1 to 1 000 l/h
• Step 12: Pass 2 to 400 l/h
• Step 13: Pass 1 to 1 000 l/h
• Step 14: Pass 2 to 450 l/h
• Step 15: Pass 1 to 1 000 l/h
• Step 16: Pass 2 to 500 l/h
• Step 17: Pass 1 to 1 000 l/h
• Step 18: Pass 2 to 550 l/h
• Step 19: Pass 1 to 1 000 l/h
• Step 20: Pass 2 to 600 l/h
Содержание WATERCLEAN 1600
Страница 2: ......
Страница 14: ...GENERAL Version 03 2008 WATERCLEAN 1600 8 ...
Страница 28: ...DESCRIPTION Version 03 2008 WATERCLEAN 1600 22 Fig 13 Anti scalant mounting kit 1 2 ...
Страница 48: ...DESCRIPTION Version 03 2008 WATERCLEAN 1600 42 ...
Страница 82: ...OPERATION Version 03 2008 WATERCLEAN 1600 76 ...
Страница 106: ...APPENDIX Version 03 2008 WATERCLEAN 1600 100 ...
Страница 108: ......
Страница 110: ......