CAN RANGER III INSTALLATION
16
actuator is not functioning
correctly. Try the other
handles to see if the one of
the other handles control the
displayed position. If so, swap
the actuator locations or re-ID
the actuators. If no handle
controls the position, make
sure the actuators are linked
to the valves.
If the ACTUATOR 1 handle can
change the position on the
display, center the handle. It
should be about 1.5 inch.
Note that the actuator total
travel is 3 inch; therefore 1.5
is the center position. If it is
not close, adjust the linkage
to the valve handles and push
<SET>.
Center Calibration Screen
The next screen will be to set
the Fast Forward. Push the
ACTUATOR 1 Handle all the
way in the direction for
Forward. Hold it there and
push <SET>.
Fast Forward Calibration Screen
Next the Slow Forward needs
to be set. Hold the ACTUATOR
1 Handle in the position for
slow Forward, and press
<SET>.