3. Check the permitted disconnect time for the overload protection cut-out if a fault arises.
4. Use conductor dimensions and fuse ratings in accordance with local regulations (in Germany
VDE 0100 parts 430 and 523, for example).
5. The user must provide the machine with a lockable power supply disconnecting device.
This could be, for example, a load disconnect switch with fused input. If a circuit breaker is used
it must be suitable for the motor starting characteristics.
Machines with a total power rating of up to 3 kW and rated current of up to 16 amps may be
provided with a simple cable and plug power supply connection.
DANGER
Danger of fatal injury from electric shock!
➤ Switch off and lock out the power supply disconnecting device and check that no voltage is
present.
6. Connect the machine to the power supply.
6.7 Options
The options available for your machine are described below.
6.7.1 Option C5
Oil level monitoring
The oil level monitor does not relieve the user of the obligation to visually check the oil level at
regular intervals.
The contact in the oil level monitor is wired at the factory as a normally open contact.
Oil level
Electrical contact
rises
closes
falls
opens
Tab. 31 Oil level monitor
Precondition The supply disconnecting device is switched off,
the device is locked off,
the absence of voltage has been verified.
DANGER
Electric shock!
Danger of fatal injury caused by contact with live components.
➤ Switch off and lock out the power supply disconnecting device and verify the absence of voltage.
6
Installation
6.7
Options
No.: 9_5753_04 E
Assembly and operating manual 2-stage piston compressor
EPC-2-G
35