No. Grid
LED
LED
Display
Status description
Action
Pers
.
94
Self test error buffer 2
The control board is defective.
Notify authorised
electrician / KACO
Service!
E/K
95
Relay 1 self test error
The power section is defective.
Notify KACO Service K
96
Fehler Selbsttest Relais 2
The power section is defective.
Notify KACO Service K
97
Protection shutdown over-
current HW
Too much power has been fed into the grid.
Complete disconnection of the device.
Notify authorised
electrician / KACO
Service!
E/K
98
Protect. shutdown HW gate
driver
An internal protective mechanism has discon-
nected the device to protect it against dam-
age. Complete disconnection of the device.
Notify authorised
electrician / KACO
Service!
E/K
67
Fault at power section 1
There is a fault in the power section.
Notify your author-
ised electrician!
E
99
Protect. shutdown HW buf-
fer free
An internal protective mechanism has discon-
nected the device to protect it against dam-
age. Complete disconnection of the device.
Notify authorised
electrician / KACO
Service!
E/K
100
Protect. shutdown HW over-
heating
The device has been switched off because the
temperatures in the housing were too high.
Check to make sure
that the fans are
working. Replace
fan if necessary.
B E
101
Plausibilitätsfehler Temper-
atur
The device has shut down because of implaus-
ible internal measured values.
KACO-Service bena-
chrichtigen!
K
102
Plausibilitätsfehler
Wirkungsgrad
The device has shut down because of implaus-
ible internal measured values.
KACO-Service bena-
chrichtigen!
K
103
Plausibilitätsfehler Zwis-
chenkreis
The device has shut down because of implaus-
ible internal measured values.
KACO-Service bena-
chrichtigen!
K
104
Plausibility fault AFI module The device has shut down because of implaus-
ible internal measured values.
KACO-Service bena-
chrichtigen!
K
105
Plausibility fault relay
The device has shut down because of implaus-
ible internal measured values.
KACO-Service bena-
chrichtigen!
K
106
Plausibility error DCDC con-
verter
The device has shut down because of implaus-
ible internal measured values.
KACO-Service bena-
chrichtigen!
K
107
Check surge protection
device
Surge protection device (if present in the
device) has tripped and must be reset if appro-
priate.
Check functional
display of surge pro-
tection device. Ob-
serve application
note on the KACO
website: Installing
overvoltage protec-
tion.
K
121
Door open
The door is open. The unit has interrupted the
feed-in.
Close door. Check
the contact switch
for free movement.
E
Powador 30.0-72.0 TL3