Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Q constant
0 – 100%
More detailed information about the procedure can be found at:React-
ive power control [See section 10.1
F
Set the idle power Q (in %) to a fixed value.
Under-excited | over-
excited
F
Select the type of phase shift.
NOTE: Under-excited relates to inductive load, over-excited relates to
capacitive load.
4
1
2
3
4
cos-phi(P/Plim)
NOTE: More detailed information about the procedure can be found
at:
Reactive power control [See section 10.1
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
4
1
2
3
4
Settling time
1s – 120 s
F
Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient re-
sponse corresponds to a first-order filter (PT-1) with settling time =
5Tau.
4
1
2
3
4
Lock-in voltage
23V – 287V
F
Set the voltage above which control is activated.
4
1
2
3
4
Lock-out voltage
23V – 287V
F
Set the voltage below which control is deactivated.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F
Specify the number of nodes for the cos ϕ /(p/pn).
4
1
2
3
4
1st node … 10th node
Voltage | Reactive
power | Excitation
0-100%
F
Power factor for 1st ,10th ... node as a percentage of the maximum
power.
1 – 0.3
F
Specify the
NOTE: cos ϕ
of the node.
Over-excited | un-
der-excited
F
If a reactive power not equal to 1 is selected: Select the type of
phase shift.
4
1
2
3
4
Q(U) 10 nodes
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
NOTE: More detailed information about the procedure can be found
at:
Reactive power control [See section 10.1
4
1
2
3
4
Settling time
1s – 120 s
F
Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient re-
sponse corresponds to a first-order filter (PT-1) with settling time =
5Tau.
4
1
2
3
4
Lock-in power
0 – 100% S
max
F
Set the active power as % of rated power above which control is ac-
tivated.
4
1
2
3
4
Lock-out power
0-100% S
max
F
Set the active power as % of rated power below which control is de-
activated.
4
1
2
3
4
Lock-in time
0 s – 60 s
F
Set the length of time that the active power must remain below the
lock-in power level before control is activated.
Powador 30.0-72.0 TL3
Page 45
EN