Powador 39.0
TL3
Powador 39.0
TL3 M1
Powador 60.0
TL3
Powador 60.0
TL3 - XL - F -
SPD 1+2 OP
Powador 48.0
TL3 Park
Powador 72.0
TL3 Park
Contribution to peak short-cir-
cuit current ip
132 A
Initial short-circuit alternating
current (Ik" first single period
effective value)
51.1 A
76.9 A
51.1 A
76.9 A
Short circuit current continu-
ous [ms] (max output fault
current)
45 A
73.4 A
45 A
73.4 A
Inrush current
98 A [RMS (20ms)]
Rated frequency
50/60 Hz
Frequency range
45 - 65 Hz
Reactive power
0-100 % Snom
cos phi
0.3 - 1 ind/cap
Number of feed-in phases
3
Distortion factor (THD)
< 3 %
Max. voltage range (up to 100
s)
520 V (Ph-Ph)
588 V (Ph-Ph)
AC overvoltage protection
M: to be provided externally on-site
XL: installed internally, Type III, 1 per MPP tracker
XL SPD 1+2: installed internally, Type I+II, 1 per MPP tracker
*) The device is designed for use exclusively on the medium-voltage grid.
4.2
General Data
Powador 39.0
TL3
Powador 39.0
TL3 M1
Powador 60.0
TL3
Powador 60.0
TL3 - XL - F -
SPD 1+2 OP
Powador 48.0
TL3 Park
Powador 72.0
TL3 Park
General electrical data
Max. efficiency
98.0 %
97.80 %
98.0 %
European efficiency
97.80 %
97.50 %
97.90 %
97.80 %
Self consumption: Standby
1.5 W
Feed-in from
120 W
Transformer unit
no
Protection class / over voltage
category
Grid monitoring
0
Distribution system
TN-C-System, TN-C-S-System, TN-S-System, TT-System
Powador 39.0
TL3
Powador 39.0
TL3 M1
Powador 60.0
TL3
Powador 60.0
TL3 - XL - F -
SPD 1+2 OP
Powador 48.0
TL3 Park
Powador 72.0
TL3 Park
General Data
Display
Graphical display 240 x 128 LEDs
Controls
4-way 2 buttons
Menu languages
DE; EN; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
Interfaces
Ethernet, USB, RS485, S0 output, digital input “Inverter off"
Communication
TCP/IP, Modbus TCP, Sunspec
Potential-free relay
Potential-free NO contact, max. 230 V / 1 A
DC isolator switch
yes
Powador 30.0-72.0 TL3