Vendor
The display shows information about the device manufacturer.
9.4.2
Configuration via web user interface
NOTE
In addition to the parameters in the chapterMenu [See section 9.4.1
Page 37], additional parameters are
available and accessible via the web user interface. To do so, enable
Remote config
in
Network
un-
der
Webserver
and enter the device IP address into your browser.
4
1
2
3
Operating settings
NOTE: Options for advanced setting of the operating parameters.
4
1
2
3
DC starting volt.
The device begins feed-in as soon as this DC voltage is present.
F
Set the starting voltage.
4
1
2
3
Const.volt.reg.
NOTE: Option to disable the MPP seek mode in order to operate the
device with a constant DC voltage.
1 Activate or disable the constant voltage controller.
2 Set value for constant voltage controller.
4
1
2
3
Iso.resistance
F
Set threshold value (in 1kOhm increments) at which the insulation
monitor reports a fault.
4
1
2
3
4
FRT (Fault Ride
Through)
NOTE: The device supports dynamic grid stabilization (Fault Ride-
Through)
.
NOTE: More detailed information at:
4
1
2
3
4
Operation mode – On
| Off
F
Select a control process.
On: Activates dynamic grid support using dynamic reactive current.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Settings | Manual |Pre-
defined zero current
F
Select a control process.
Priority – Reactive cur-
rent limitation | Dy-
namic reactive current
F
Select a control process.
4
1
2
3
4
Constant K positive se-
quence dip &
Constant K positive se-
quence swell
k 0 – 10 2
F
Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Constant K negative se-
quence dip
Constant K negative se-
quence swell
k 0 – 10 2
F
Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
4
1
2
3
4
Dead band
0 - 100 [% Uref]
10.0
F
Set dead band in %.
4
1
2
3
4
Dynamic reactive cur-
rent only
Off | On
NOTE: With FRT mode activated, the pre-fault reactive current can be
added.
F
If necessary, activate pre-fault reactive current.
Powador 30.0-72.0 TL3
Page 47