4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
200– 120,000 [ms]
F
Specify the settling time.
4
1
2
3
4
Active curve
1 - 5
F
Select active curve.
NOTE: Up to 5 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Number of nodes
2 – 5
F
Specify the number of nodes.
Power
0.0 -100.0 [%]
F
Specify power for 1st, 5th ... node as a percentage of the maximum
power.
Voltage
0.0 -126.0 [%]
Password protection
Status
1 Specify voltage for 1st, 5th ... node as a percentage of the maximum
voltage.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Activation threshold
230V – 276V
F
Specify the activation threshold.
NOTE: If the 10 min mean value of the voltage exceeds the activation
threshold, then the function is enabled. The power level is adjusted in
such a way that the instantaneous effective voltage value does not ex-
ceed the activation threshold value.
4
1
2
3
4
Deactivation threshold
230V – 276V
NOTE: If the 10 min mean value of the voltage falls below the de-
activation threshold, then the function is disabled.
1 Specify the deactivation threshold.
4
1
2
3
Upload/download
NOTE: Opportunity to save log files and save and import parameter
data
Download service log
data
F
Save service log data to external storage media.
Download service log
data without yields
F
Save log data without yields to external storage media.
Download a set of
parameters
F
Save a set of parameters to external storage media.
Document a set of
parameters
F
Issue or print documentation of a set of parameters as a PDF.
Transfer a set of para-
meters
F
Load a set of parameters from external storage media.
NOTE
With regard to the selection of country settings, KACO new energy attests:
›
that the relevant certificates are only valid if the corresponding country settings have been selected.
›
that all configured grid parameters must be configured in accordance with the requirements of the
grid operators.
›
that the configuration of parameters using IEEE 1547: 2003 table 1 is possible but is only permitted if it
is requested by the grid operators.
Powador 30.0-72.0 TL3
Page 51
EN