NOTE
Dimensioning the PV generator
The device is designed with a reserve of DC short-circuit current resistance. This enables an overdimension-
ing of the connected PV generator The absolute limit for the PV generator is the value of the maximal short
circuit current (ISCmax.) and the maximal open circuit voltage (Uoc max). See Footnote under Electrical
data [See section 4.1
7.6.5
Connecting the PV generator
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death will result if the live connections are touched. When there is sunlight present on the
PV generator, there is DC voltage on the open ends of the DC cables.
›
Only touch the PV generator cables on the insulation. Do not touch the exposed ends of the cables.
›
Avoid short circuits.
›
Do not connect any strings with a ground fault to the device.
DC-
DC+
DC+
DC-
DC+
DC-
String 1
String 2
String 3
1
C
1
0
1
C114
S
G
1
0
2
C
1
1
8
PE
VR102
C107
PV1
VR101
PE
C106
VR104
C
1
1
0
C115
VR103
VR106
C124
PV3
PE
SG105
C123
1
0
3
S
G
1
0
6
S
G
1
0
1
PE
PV2
S
G
1
0
4
VR105
C
1
0
1
C114
S
G
1
0
2
C
1
1
8
VR102
C107
VR101
C106
VR104
C
1
1
0
C115
VR103
VR106
C124
SG105
C123
1
0
3
S
G
1
0
6
S
G
1
0
1
S
G
1
0
4
VR105
1
C
1
0
1
C114
S
G
1
0
2
C
1
1
8
PE
VR102
C107
PV1
VR101
PE
C106
VR104
C
1
1
0
C115
VR103
VR106
C124
PV3
PE
SG105
C123
1
0
3
S
G
1
0
6
S
G
1
0
1
PE
PV2
S
G
1
0
4
VR105
C
1
0
1
C114
S
G
1
0
2
C
1
1
8
VR102
C107
VR101
C106
VR104
C
1
1
0
C115
VR103
VR106
C124
SG105
C123
1
0
3
S
G
1
0
6
S
G
1
0
1
S
G
1
0
4
VR105
1
C
1
0
1
C114
S
G
1
0
2
C
1
1
8
PE
VR102
C107
PV1
VR101
PE
C106
VR104
C
1
1
0
C115
VR103
VR106
C124
PV3
PE
SG105
C123
1
0
3
S
G
1
0
6
S
G
1
0
1
PE
PV2
S
G
1
0
4
VR105
C
1
0
1
C114
S
G
1
0
2
C
1
1
8
VR102
C107
VR101
C106
VR104
C
1
1
0
C115
VR103
VR106
C124
SG105
C123
1
0
3
S
G
1
0
6
S
G
1
0
1
S
G
1
0
4
VR105
Fig. 32:
DC connection to power board
Connecting the PV generator
↻
PV generator is dimensioned according to the performance characteristics of the unit.
1 Undo the cable fittings [ W_46].
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Strip the insulation from the DC cables.
5 Screw the cable ends of the PV generator onto the DC connection according to the polarity of the battery.
6 Check secure fit of all connected cables.
7 Remove the protection against contact from the PV+ and PV- terminal.
8 Tighten the cable fittings [ W_46 / 10 Nm].
»
The device is connected to the PV generator.
7.7
Connecting the interfaces
7.7.1
Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death may result from improper use of the interface connections and failure to observe
protection class III.
›
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with pro-
tection class III.
Powador 30.0-72.0 TL3
Page 28
EN